Technical Specifications : |
Model |
SI8910 |
SI8915 |
SI8920 |
SI8930 |
SI8940 |
SI8960 |
SI8980 |
SI89100 |
SI89120 |
SI89160 |
SI89200 |
VA Rating |
10KVA |
15KVA |
20KVA |
30KVA |
40KVA |
60KVA |
80KVA |
100KVA |
120KVA |
160KVA |
200KVA |
Operating Mode and Principle |
True on-Line, Static Bypass(Uninterruptible Switch), Dual Conversion, Output Galvanic isolate |
AC Input |
Phase |
3 Phase + N + G |
Voltage |
380V+-25% |
Frequency |
50/60Hz+-5% |
P.F. |
0.92 |
Soft Start |
0~100% 5s |
Bypass Input |
Phase |
3 Phase + N + G |
Voltage |
380V+-25% |
Frequency |
50/60Hz+-5% |
Transfer Time |
0ms, Inverter/Bypass (Overload) |
DC System |
Voltage |
360V (Rated Voltage) |
405V (Float Charge Voltage) |
315V (Shutdown Voltage) |
Current (A) |
28 |
42 |
56 |
85 |
113 |
169 |
225 |
282 |
338 |
381 |
507 |
Charge Current |
1A~30A (Adjustable, Depend on battery) |
AC Output |
Phase |
3 Phase + N + G |
Voltage |
380V+-1% (Stable Load); 380V+-5% (Fluctuated Load) |
Frequency |
50~60Hz+-0.05Hz (Battery mode) |
P.F. |
0.8 |
Waveform |
True Sine Wave |
Distortion |
Total Harmonic Distortion: <3%(Linear Load);<5%(Non-Linear Load) |
Time |
Transient Recovery Time: <10ms |
Overload |
125% for 10 Minute; 150% for 1 Minute |
Cooling |
Force Wind |
System |
Efficiency |
91% |
95% |
Interface |
RS232, SNMP (Optional) |
Temperature |
0~40 C (Operating) |
Humidity |
30~90% |
Optional |
Isolation Transformer |
Harmonic Suppression Filter |
Two Modules Parallel |
Noise(dB) |
48~60 |
53~65 |
55~65 |
60~65 |
Dimension(mm) WxDxH |
450x730x1140 |
450x855x1140 |
710x855x1500 |
1100x860x1680 |
1800x1100x1680 |
Net weight(kg) |
208
|
220 |
240 |
316 |
334 |
650 |
900 |
950 |
1050 |
2100 |
3200 |
Packing Dimension(mm) |
520x800x1300 |
520x930x1400 |
780x940x1660 |
1180x940x1850 |
1880x1180x1850 |
Gross weight(kg) |
232 |
248 |
265 |
346 |
364 |
695 |
965 |
1015 |
1115 |
2195 |
3295 |
|
copyright © 2011, Silic Stable Service Co.,ltd. All